Cooling
Next Generation Data has designed its cooling utilising the latest technologies. All environments will be CFD modelled prior to build to ensure optimum air flow and cooling throughout in conjunction with customer requirements.
A resilient Chilled Water system enhanced by free cooling following the external ambient temperature will be used throughout the facility.
Cooling Highlights
  • Data halls will be maintained at 24 degree Celsius +/- 2 degrees
  • Data hall humidity to be maintained at 50% +/- 10%
  • Dual feed Chilled water ring
  • N+20% on Computer Room Air Conditioning Units (CRACS)
  • Concurrently maintainable paths
  • Zoned temperature and Humidity monitoring
  • Fully bunded System
  • Leak detection on all distributed pipe work
 